ZR & ZP Copeland Scroll™ Compressor Range for air-conditioning

Model Cooling capacity on R407c, condensation temperature =+40°C, boiling temperature= +5°C Displacement (m3/h) Stub Suction (inch) Stub discharge (inch) Length/Width/Height (mm) Net weight (kg) Maximum operating Current (А) Sound Pressure 1м-d(BA)**
3 phase*
ZR22K3E 5.2 kW 5.3 3/4" 1/2" 242/242/363 22 4 54
ZR28K3E 6.7 kW 6.8 3/4" 1/2" 242/242/363 25 5 54
ZR34K3E 7.9 kW 8.0 3/4" 1/2" 242/242/386 26 6 57
ZR40K3E 9.4 kW 9.4 3/4" 1/2" 242/242/400 27 7 57
ZR48K3E 11.5 kW 11.4 7/8" 1/2" 242/242/417 31 10 57
ZR61KCE 14.4 kW 14.4 7/8" 1/2" 241/247/451 43 11 60
ZR72KCE 16.9 kW 17.1 7/8" 1/2" 242/242/438 39 13 61
ZR81KCE 19.1 kW 18.7 7/8" 3/4" 242/242/446 39 15 61
ZR94KCE 23.3 kW 22.1 1-1/8" 7/8" 264/285/476 57 16 63
ZR108KCE 26.2 kW 24.9 1-3/8" 7/8"  264/285/533 60 17 63
ZR125KCE 30.5 kW 29.1 1-3/8" 7/8"  264/285/533 61 19 63
ZR144KCE 35.0 kW 33.2 1-3/8" 7/8"  264/285/533 61 22 64
ZR160KCE 38.7 kW 36.4 1-3/8" 7/8"  264/285/552 65 28 67
ZR190KCE 44.7 kW 43.3 1-3/8"  7/8"  264/285/552 66 34 69
ZR250KCE 59.3 kW 56.6 1-5/8" 1-3/8" 432/376/717 140 41 72

 * 3 phases: 380-420 V/ 50 Hz

** 1m: sound pressure level at 1m distance from the compressor, free field condition

Model Cooling capacity on R410A, condensation temperature =+40°C, boiling temperature= +5°C Displacement (m3/h) Stub Suction (inch) Stub discharge (inch) Length/Width/Height (mm) Net weight (kg) Maximum operating Current (А) Sound Pressure 1м-d(BA)**
3 phase*
ZP42K5E FOR R410A 10.5 kW 6.9 3/4" 1/2" 242/242/398 31 8 57
ZP54K3E FOR R410A 13.5 kW 8.9 7/8" 1/2" 242/242/443 34 10 59
ZP61K5E FOR R410A 15.5 kW 10 7/8" 1/2" 246/246/443 35 12 60

 * 3 phases: 380-420 V/ 50 Hz

** 1m: sound pressure level at 1m distance from the compressor, free field condition

Firma "Revers" LTD doesn't grant any warranties regarding the technical characteristics and parameters specified in this home page, and assumes no liability for any damages of any nature arising from the use of information provided here. Mentioned here Technical data and pictures are informative, and errors and misprints are not excluded.